Fire alarm cable is a life-safety cable class. It differs fundamentally from data cables that carry information and instrumentation cables that carry signals: when those fail, the loss is commercial. When this fails, the loss is human. At the moment a fire starts, whether the alarm system operates, whether sounders achieve adequate output, whether voice evacuation messages remain intelligible and whether ancillary equipment sequences correctly all depend on this cable still being intact under the worst possible conditions. Selection criteria are therefore far stricter than for general wiring cable, and downgrading on a "good enough" basis is never acceptable.
This range connects fire alarm control panels to field devices: smoke detectors, heat detectors, flame detectors, manual call points, sounders and beacons, emergency loudspeakers and signage, input/output modules, and ancillary control equipment such as fans, smoke dampers, fire shutters and pump sets.
Cable requirements divide into four circuit functions, each with different technical priorities:
• Signalling Line Circuits (SLC) connect addressable devices and carry digital communication data. Conductor size is not demanding, but signal integrity and loop capacity are.
• Notification Appliance Circuits (NAC) drive sounders and loudspeakers. Current is higher and runs are longer, making this the circuit most vulnerable to voltage drop and the one that usually requires larger conductors.
• 24 V power circuits supply field modules and devices, again requiring voltage drop verification against load and distance.
• Control circuits drive high-power actuators such as smoke dampers, shutters and fans; core count and size follow the controlled equipment.
By system type, conventional zoned systems identify alarm locations through physical zones, with each zone forming its own circuit — more cable, but simple and economical. Addressable systems hang dozens or hundreds of individually addressed devices on one loop pair, using far less cable and giving precise fault location; this is now the mainstream for new construction. The two impose clearly different demands on core count and construction, so the system type must be confirmed before cable is selected.
Matching conductor size to voltage drop is the most commonly overlooked and most commonly botched aspect of fire alarm cable selection. NAC runs often span an entire floor or building, and end-of-line sound pressure level must meet the design requirement — which depends on the voltage actually arriving at the device. Longer runs and smaller conductors mean greater drop, and sounders may then fail to achieve rated output. Conductor sizing must be calculated by the project designer against the applicable code, load and run length; it cannot be taken from habit. Multi-core constructions (4-core, 6-core) integrate several circuits into one cable, materially reducing conduit runs and installation hours, and are common on large projects.
Jackets are offered in PVC and LSZH. LSZH produces low smoke density and no corrosive hydrogen halide gases when burned, and is recommended or mandated in enclosed, high-occupancy locations — basements, high-rise escape routes, hospitals, cinemas, metros and airports. In these locations smoke itself is the leading cause of death, and jacket material matters far beyond the cost difference.
Products in this range can be supplied against the applicable requirements of EN 50200, IEC 60331, UL 2040, BS 5839 and GB/T 19666. One point requires emphasis: fire resistance class, flame retardance class, specific certifications and test reports must be taken from formal documentation issued by the factory for the product actually supplied. Buyers should state the class required by the project and request the corresponding evidence, rather than accepting a generic material statement in its place.
As Custom Fire Alarm Wiring Cable Manufacturers, Hangzhou Linan Jiaheng Cable Co., Ltd. supplies a life-safety cable range for fire detection and alarm systems. We manufacture 2-core, 4-core and 6-core fire alarm wiring in PVC and LSZH jackets, with unshielded or screened constructions, for detector circuits, notification appliance circuits, control wiring and conventional zoned detection. These cables connect fire alarm control panels to detectors, manual call points, sounders, beacons, input/output modules and ancillary plant such as smoke dampers and fans.
Fire alarm cable differs from data and instrumentation cable in a fundamental way: failure is measured in human terms, not commercial loss. That is why the range is built around conductor sizing, jacket behaviour, colour identification and circuit segregation. We offer OEM-focused, factory-direct supply for projects where documentation and consistency are as important as the copper itself.
The table below summarises our standard fire alarm cable range and the circuit type each construction is designed to serve.
| Product | Conductor | Jacket / Screening | Typical Circuit Fit |
|---|---|---|---|
| 2 Core 14AWG LSZH Fire Alarm Cable | 14AWG ≈ 2.08 mm² | LSZH, unshielded | Notification appliance circuits, sounder loops and 24 V power circuits over long runs |
| 2 Core 18AWG PVC Fire Alarm Cable | 18AWG ≈ 0.82 mm² | PVC, unshielded | Detector branches, manual call points and short signalling circuits in non-public areas |
| 4 Core 18AWG LSZH Unshielded Fire Alarm Cable | 18AWG ≈ 0.82 mm² | LSZH, unshielded | Conventional zoned detection systems, detector and auxiliary circuits in occupied areas |
| 6 Core 18AWG Fire Alarm Cable | 18AWG ≈ 0.82 mm² | PVC or LSZH per order; shield to confirm | Multi-circuit zoned detection, control wiring, module power and signal combination |
These cables can be supplied against the applicable requirements of EN 50200, IEC 60331, UL 2040, BS 5839 and GB/T 19666. The specific fire-resistance class, flame-retardance class and test evidence must be identified at ordering stage; we confirm the factory documentation that applies to the cable actually produced. Where a project requires screened fire alarm cable, we can supply an overall foil shield or another construction to match the specification.
Conventional zoned systems detect fire by physical zone, so each zone forms its own circuit. They are simple and economical, but multiple circuits along the same route demand multi-core cable if containment and installation time matter. Addressable systems place many individually addressed devices on one loop pair, using less cable overall, but loop performance depends on total conductor resistance and capacitance.
Within either architecture, four circuit functions drive cable selection:
Voltage drop is current multiplied by conductor resistance. A 14AWG conductor has roughly two and a half times the cross-section of 18AWG, so its resistance per metre is proportionally lower. On a long NAC run, that difference can determine whether the last sounder receives enough voltage to achieve the required sound pressure level. A circuit can report healthy at the panel while the far end operates below rating.
Conductor sizing must be calculated by the project designer against the applicable code, total appliance load, route length, installation method and end-of-line voltage requirement. We provide conductor resistance, capacitance and physical data for the calculation; the sizing decision and compliance responsibility sit with the designer and approving authority.
Jacket material is a project decision, not a price decision. We supply both:
When a project is mixed-use or uncertain, LSZH is the safer default because fire alarm cable runs along the routes people use to evacuate.
Four-core and six-core fire alarm cables reduce the number of pulls, entries into panels and supports, and they simplify cable schedules. On six-core cables, common allocations include three detector zone pairs, two detector circuits plus one sounder circuit, or a zone pair plus power and control pairs for remote modules. The allocation must be fixed on circuit diagrams before installation, not improvised on site.
Confirm colour coding at ordering stage and record it in the as-built documentation. A reversed pair can be diagnosed quickly; a core connected into the wrong circuit can leave a zone unmonitored and defeat the safety function. Fire alarm circuits must also be segregated from power circuits by separation or containment. A multi-core fire alarm cable is treated as a single fire alarm circuit for segregation purposes, which is simpler to route than several individual cables.
Jiaheng Cable Co., Ltd. was founded on January 23, 2008, in Hangzhou and evolved from coaxial cable production into a specialised cable manufacturer integrating R&D, manufacturing and sales. We operate as a China-based fire alarm cable manufacturer and supplier and are committed to OEM supply with zero channel conflict: our partners' brands, customers and pricing remain protected.
For each order we can provide copper purity certificates, insulation compound datasheets and pre-shipment QC reports with photos and test data. Material documentation is matched to the cable actually produced, and our engineer follows the job from specification through to production. Fire resistance and flame-retardance claims are backed by factory documents for the supplied product, never by a generic material statement.
To prepare a proposal and production routing, we need the following project inputs:
Yes. Our 2 Core 14AWG LSZH Fire Alarm Cable is designed for NAC and sounder loops. Its larger conductor reduces voltage drop over long runs, and the LSZH jacket is suited to occupied buildings and escape routes. We can also supply 18AWG LSZH constructions for detector and conventional zone circuits.
18AWG has a nominal cross-section of about 0.82 mm² and is normally adequate for detector branches, call points and short signalling runs. 14AWG is about 2.08 mm² and is used where appliance current and distance make voltage drop the controlling factor. The right size should always be confirmed by calculation.
In many conventional and mixed installations, yes. Six cores can support three detector zones, two detector circuits plus one sounder circuit, or a combination of signal, power and control pairs. The core allocation must be documented before installation, and segregation from power circuits must still be respected.
Yes. Documentation is issued for the cable actually produced. When you specify the required fire resistance and flame-retardance class, we confirm the applicable factory reports and material datasheets before shipment. We also provide pre-shipment QC reports with photos and test data.
Yes. We are an OEM-focused manufacturer. Core count, conductor size, jacket material, shielding, colour coding, drum length and printing can be adapted to your project or brand. We work with distributors and installation contractors to match the specification and packaging to the destination market.